A new fuzzy framework for the optimal placement of phasor measurement units under normal and abnormal conditions
This paper presents a new procedure for finding the optimal placement of the phasor measurement units
(PMUs) in modern power grids to achieve full network observability under normal operating conditions,
and also abnormal operating conditions such as a single line or PMU outage, while considering the availability
of PMU measuring channels. The proposed modeling framework is implemented using the fuzzy
binary linear programming (FBLP) technique. Linear fuzzy models are proposed for the objective function
and constraints alike. The proposed procedure is applied to five benchmark systems such as the
IEEE 14-bus, 30-bus, 39-bus, 57-bus, and 118-bus. The numerical results demonstrate that the proposed
framework is capable of finding a fine-tuned optimal solution with a simple model and acceptable solution
characteristics compared with early works in the literature. Besides, four evaluation indices are
introduced to assure the various criteria under study such as the observability depth, measurement redundancy,
and robustness of the method under contingencies. The results show that full network observability
can be met under normal conditions using 20% PMUs penetration; however, under contingencies,
approximately 50% PMUs penetration is required. The novelty of the proposed procedure has proven the
capability of the proposed linear fuzzy models to find better optimal number of PMUs with lower number
of channels compared to other algorithms under various operating conditions. Hence, the proposed
work represents a potential tool to monitor power systems, and it will help the operators in a smart grid
environment.
Keywords:
Binary linear programming, Fuzzy models, Observability, Optimization, Phasor measurement unit, Smart grids